Model | GSA96 | GSA192/220 | ||
Output Power(KVA)
|
6/8
|
6/10/15
|
20/25/30
|
|
Battery
|
||||
Rated Voltage (VDC)
|
96
|
220
|
||
Low Voltage Protective Value(VDC)
|
86.4
|
194.4
|
||
Low voltage recovery value(VDC)
|
104.0
|
234.0
|
||
Over voltage protective value(VDC)
|
124.0
|
279.0
|
||
Over voltage recovery value(VDC)
|
120.0
|
270.0
|
||
PV Input
|
||||
Maximum Input Power(KWP)
|
5.7
|
12.8/25.6
|
||
Maximum Charge Current(A)
|
50/100
|
|||
Start Voltage(VDC)
|
120
|
270
|
||
MPPT Voltage Range(VDC)
|
110-280
|
260-450
|
||
Maximum Open Circuit Voltage(VDC)
|
300
|
480
|
||
Floating Voltage(VDC)
|
Adjustable
|
108.0
|
243.0
|
|
Bulk Charge Voltage(VDC)
|
113.6
|
255.6
|
||
Ac bypass(Optional)
|
||||
Allowable Input Voltage Range(VDC)
|
220±15%/110±15%Other input voltage (can be customized)
|
|||
Input Frequency(HZ)
|
50/60±3%
|
|||
AC charger
|
Optional
|
|||
AC Output
|
||||
Output Waveform
|
L+N Pure Sine Wave
|
|||
Output Voltage
|
220VAC±1%;110VAC±1%(Other output voltage can be customized)
|
|||
Output Frequency(HZ)
|
50/60±1%
|
|||
Output waveform distortion rate(THD)
|
≤2%(Liner Load)
|
|||
Convert Efficiency(80% Resistive load)
|
≥85%
|
|||
Current Peak Factor
|
3:1
|
|||
Overload Ability
|
105-110%,600Seconds;110125%,60Seconds;>125%,1Second
|
|||
Display Method
|
LCD+LED
|
|||
Protection
|
Input reverse protection;Input low voltage protection;Input over voltage protection; Output overload protection;Output short circuit protection(do not recovery automatically need to restart machine); Machine over heating protection.
|
|||
Communication Function
|
Optional
|
|||
Surroundings
|
||||
Protective Level
|
IP20
|
|||
Applied Altitude (M)
|
≤5000(above1000meters,rated power derating1% every 100meters)
|
|||
Allowable relative humidity
|
<95% Non-condensation
|
|||
Environment temperature(ºC)
|
-10~+50
|
|||
Noise(1 Meter)
|
≤50dB
|
|||
Size and weight
|
||||
D*W*H(mm)
|
650*310*770
|
650*310*770 |
690*405*980
|
|
Weight(KG)
|
55
|
55-100
|
135-155
|